The section 2214.6 that you're referring relates to Seismic Zones 1 & 2 of old UBC.

As you're awar,e the first step is to establish the SDC (Seismic Design Category) for your site. Depending on the SDC, you're forced to use either steel SCBF or OCBF.

Based on Tale 9.5.2.2 of ASCE7-02, there is no limit in using OCBF in SDC A, B and C, but there are restrict limitations in SDC D and E. However OCBF is not permitted in SDC F.

 

IBC 2003 refers to AISC 341-02, the "Seismic Provisions for Structural Steel Buildings" for steel design which was published on May 21, 2002. For OCBF connection, you'd refer to its section 14.2 but for SCBF's section 13.3.

 