The code limits l/d during construction? Whoa….where is that found?
I don't recommend a loadbearing wall of 10' in height be made of 2x4s. Why? Because the walls will not be sheathed before the floor joists are set into place. The code limits the L/d ratio to 75 for construction, and a 10' 2x4 has an L/d of 80. The contractor cannot build the wall unless he plans on bracing every stud without violating the code.
***** ****** ******* ****** ****** ********