Serviceability Requirements of Prestressed Concrete Members
18.4.2 of ACI318-99 (c) [ 6 sq rt f'c ] and (d) [ 12 sq rt f'c ] prescribes permissible tension at service loads.
18.3.3 of new ACI318-02, 05 classifies prestressed members into Class U, T and C according to f_t.
Does this mean a prestressed member classified as Class C which will have 'some cracks' definitely
can be accepted as long as it can satisfy strength requirement?
Is engineer's judgment required?
Let's take an example.
Here is a precast prestressed double tee for the parking garage.
Its strength design shows Mu/phi Mn=1.01 (phi Mn /Mcr=1.4).
Tensile stress (service load) at the midsection is -12000 psi
while 12 sq rt f'c is -950psi.
Camber is 0.5" downward and its overall length is 60ft.
Do you think this design can be acceptable?
--