Thursday, September 27, 2007

RE: Core Hole Through PT Slab

Farzin,

 

We typically will let them get within an inch on the regular reinforcing, but hold 3 inches clear of the PT just for safety.   If you have to relax the three inch you can, but that’s the rule we use.  Even with x-ray and GPR there is room for error.

 


From: FSRahbar@aol.com [mailto:FSRahbar@aol.com]
Sent: Thursday, September 27, 2007 2:57 PM
To: seaint@seaint.org
Subject: Core Hole Through PT Slab

 

List:

 

At one of our projects, the contractor needs to core some holes through the structural slab. The slab has both PT cables and regular reinforcing. Cores are from 2" to 4" in diameter and are 16" to 20" apart in both directions. We are not allowing them to cut any of the reinforcing. However, I am trying to give them a guideline as to the distance from the edge of the cores to the edge of the reinforcing. I remember a 1" dimension had been discusses in the past. Is that sufficient? Any thoughts?

 