> Hello friends:
>
>
>
> I am looking for (ICBO and/or L.A. City approved) allowable shear
> values for walls sheathed with T1-11
>
>
>
> Thanks
>
If nailed through the shiplap joint, then use the values for 3/8"
sheathing. If you use 3x or double studs, then you can use the full
panel thickness of 5/8". I don't think you can use a single 2x and get
two rows of nails into it from both panels and still maintain the proper
edge distance. I worked at one place where we called out double studs
when using T1-11, but after a few site visits discovered that few of the
contractors were doing this and the city inspectors hadn't caught this.
I then changed jobs and got out of residential work.
******* ****** ******* ******** ******* ******* ******* ***