Can he get the steel to Morgan Hill, CA cheaper than the local steel guy? I'd like to get you that beer if possible :-) Tell him to buy you one anyway, he's your brother!
-g
On 10/5/07, Gary L. Hodgson and Assoc. <ghodgson@bellnet.ca> wrote:
Gerard,
Go with as thick a member as you can. All those rules about local
buckling apply. For example, instead of a L4x4x1/4, use an L2.5
x2.5x3/8 and instead of MC10x8.4, use the heaviest 6" or 8" standard
channel, you can get. The lighter members will end up looking like a
krinkle potato chip--not that there is anything wrong with krinkle
potato chips.
You can google Hodgson Custom Rolling for further advice although I am
sure there are other rolling suppliers. If you buy something, then my
brother will buy me a beer.
Gary
Gerard Madden, SE wrote:
> I've got a curved CMU wall with a tight radius (5.5 ft) that I need to
> provide a ledger for metal deck w/ concrete fill (on inside of curve)
>
> The CMU wall continues up above the slab to form a parapet/guardrail
> (it's a landing on an exterior stairwell).
>
> I was thinking that radius-ing an angle would be difficult (to
> maintain flatness) since it's not doubly symmetric, but maybe it's
> done all the time???
>
> What about radius-in a MC10x8.4 with the toes going toward the center
> of the radius?
>
> TIA
>
> --
> -gm
******* ****** ******* ******** ******* ******* ******* ***
* Read list FAQ at: http://www.seaint.org/list_FAQ.asp
*
* This email was sent to you via Structural Engineers
* Association of Southern California (SEAOSC) server. To
* subscribe (no fee) or UnSubscribe, please go to:
*
* http://www.seaint.org/sealist1.asp
*
* Questions to seaint-ad@seaint.org. Remember, any email you
* send to the list is public domain and may be re-posted
* without your permission. Make sure you visit our web
* site at: http://www.seaint.org
******* ****** ****** ****** ******* ****** ****** ********
--
-gm