Re: AW: Boring through GLBs

Don:
According to APA EWS S560F holes up to 1 1/2" dia. may
drilled in the location you describe if used for
access & not loaded. Perhaps you can download a copy
of this document (its free) to satisfy the building
inspector.
Irv

> I have a building I designed being constructed here
> in SoCal which has a
> clear-spanned GLB floor girder system about 35 feet
> long with 36" deep
> beams. A few weeks ago I got a call from the GC
> telling me that the
> electrician, for reasons known only to the
> electrician, drilled a single 1
> ¼" diameter hole through the GLB to fish some
> conduit through to an elevator
> room. After quizzing the GC about where the holes
> were, I found that they
> were bored about 10 feet from the point of support
> and near the center of
> the depth of the beam.
>
>
>
> I was a bit miffed that it happened, but figured a
> hole that small in the
> center 1/3 of the depth of the beam away from the
> area of max moment wasn't
> going to be a big deal.
>
>
>
> Well, my engineer was extremely upset about it and
> threatened to make them
> replace the beam. He finally agreed to approve it
> but I could not get any
> impression out of him whether it really was a big
> deal structurally or if he
> was just putting on a show to teach the GC a well
> deserved lesson.
> Meanwhile, the building inspector gets into the act
> and is asking for a
> letter from the manufacturer approving the holes, an
> idea I found very odd.
>
>
>
> My question: What's going on here? What do I not
> know, after all these
> years in the biz, about holes in GLBs? From a
> reduced section standpoint,
> away from the point of max moment and near the
> center of depth, such a small
> hole seems relatively unimportant to me. Am I
> missing something?
>
>
>
> -DB
>
>


____________________________________________________________________________________
Never miss a thing. Make Yahoo your home page.

http://www.yahoo.com/r/hs

******* ****** ******* ******** ******* ******* ******* ***
* Read list FAQ at: http://www.seaint.org/list_FAQ.asp
*
* This email was sent to you via Structural Engineers
* Association of Southern California (SEAOSC) server. To
* subscribe (no fee) or UnSubscribe, please go to:
*
*

http://www.seaint.org/sealist1.asp
*
* Questions to seaint-ad@seaint.org. Remember, any email you
* send to the list is public domain and may be re-posted
* without your permission. Make sure you visit our web
* site at: http://www.seaint.org

******* ****** ****** ****** ******* ****** ****** ********