RE: Ordinary moment frame in SDC "D"

Ravi,

 

Per ASCE 7-05 Table 15.4-1, footnotes “c” & “d” allow steel ordinary moment frames for pipe racks.  You have to use bolted end plate moment connection for heights up to 60 feet, but regular connections for less than 35 feet.  Seems like this applies to your situation.

 

Doug Mayer, SE

Structural Engineer

 

From: Vasu, Ravi [mailto:Ravi.Vasu@jacobs.com]
Sent: Wednesday, September 09, 2009 2:59 PM
To: seaint@seaint.org
Subject: Ordinary moment frame in SDC "D"

 

I have a piperack with 2 levels of pipes & a platform at 34 ft from base & tie beams are at 2 levels.     

Per ASCE, table 12.2.1 does not permit ordinary moment frame for any height in "D" category for

"one story building".  Per 12.2.5.6, upto 60 ft height is allowed with roof load less than 20 psf.

 

The question is,

 

Can OMF be considered for this case in designing bracings/moment connection ?  and

 

is piperack (open structure) considered as "one story building'?

 

 

Thanks

 

 

Ravi Vasu

 


NOTICE - This communication may contain confidential and privileged information that is for the sole use of the intended recipient. Any viewing, copying or distribution of, or reliance on this message by unintended recipients is strictly prohibited. If you have received this message in error, please notify us immediately by replying to the message and deleting it from your computer.