Along the lines of what Irv noted, I've design flagpole loading per the flagpole design manufacturer's consortium (joking) design guide.  Basically, I've used the design pressures at 110 mph as a uniform load over 2 diameters and use a moment arm of 0.55h, similar to the design of a sign/billboard.  My gut says the tension on the anchors due to uplift on the canopy might govern the overall design.

On Fri, Sep 30, 2011 at 11:41 AM, IRV FRUCHTMAN <ifaeng@yahoo.com> wrote:
Joe,
I'd assume 2-d flow and calc the force per ft, on each column and for each direction as: = Cd x q x S,
where
Cd =1.2 for round column; = 2 for square column
q = dynamic pressure @ 110 mph
S = Frontal Area

Irv

--- On Fri, 9/30/11, nma <nma@nma-se.com> wrote:

From: nma <nma@nma-se.com>
Subject: Re: Wind forces on the columns of open structure
To: seaint@seaint.org
Date: Friday, September 30, 2011, 1:59 PM


Joe:

How big are the columns?  I would load up all the columns and ignore any shielding effects.  One of the things I've seen in this kind of a structure is vibration - i.e. small shaking of the whole thing.  It may also makes a small difference in the shape of the columns - round or rectangular?  You didn't say what the wind speed or exposure factor is or where the structure is located - i.e. on a hill or in the middle of a city. 

For the flying bit - I've have been criticized for larger footings than the city inspector thinks the footings should be.  But I signed for the structure and not him.   I've also seen the result of a roof flying off its supports - had my back turned with it happened.

Neil


On 9/30/2011 10:47 AM, Joseph Grill wrote:

Neil,
Thanks, I understand the flying bit.  But there is going to be a lateral wind load on the columns themselves. I am looking for the criteria to determine the horizontal load to the columns.

On Sep 30, 2011 1:38 PM, "nma" <nma@nma-se.com> wrote:
> Joe:
>
> Just figure it is going to try to fly.
>
> Neil
>
>
> On 9/30/2011 10:16 AM, Joseph Grill wrote:
>>
>> I tried to send a message yesterday on this subject. But with new
>> phones, new wireless providers, a move across country etc i'm not sure
>> it went through.
>>
>> Anyway I am designing an outdoor picnic pavilion. The plan dimensions
>> are about 60' x 30'. It will have monoslope roof supported by 4 bays
>> of 3 columns. I have calculated the wind loads for the MWFRS at the
>> roof. I can't decide on what ASCE requirements/equations to use for
>> the MWFRS loads to the columns and if that load should be applied to
>> each column in each row parallel to the load direction. In another
>> words if there are 4 columns in line parallel to the wind load would
>> all 4 columns be loaded?
>>
>> I have considered using loads calculated from section 6.5.15 "Design
>> Wind Loads on Other Structures". Am I wrong? If so can anyone suggest
>> what i should be doing?
>>
>> Thanks,
>> Joseph R. Grill, PE
>>
>
>
> ******* ****** ******* ******** ******* ******* ******* ***
> * Read list FAQ at: http://www.seaint.org/list_FAQ.asp
> *
> * This email was sent to you via Structural Engineers
> * Association of Southern California (SEAOSC) server. To
> * subscribe (no fee) or UnSubscribe, please go to:
> *
> * http://www.seaint.org/sealist1.asp
> *
> * Questions to seaint-ad@seaint.org. Remember, any email you
> * send to the list is public domain and may be re-posted
> * without your permission. Make sure you visit our web
> * site at: http://www.seaint.org
> ******* ****** ****** ****** ******* ****** ****** ********




--
David Topete, SE